Plan showing the dimensions and calculations for a transformer's iron core, primary, and secondary windings.


Identifier  ExFiles\Box 32\4\  Scan002
Date  19th August 1919 guessed
  
X.1581
Plan showing dimensions of iron, primary & secondary windings - Transformer - (used on = 220/45v.)

Top Diagram Dimensions:
3.81 cms
2.54 cms
3.49 cms
5.08 cms
14.15 cms
1.44
1.24
1.43
.35

Left Diagram Dimensions:
16.51 cms
(11.43)(10) cms

Bottom Left:
Gross C.S. Area of core
3.00 sq inches.

Calculations:
Primary
Length of mean turn = 22.35 cms
Gauge = 23. (D.C.C.)
Length of Primary wire = 22.35 x 1390
= 31,100 cms.
= 12,250 inches
= 1022 feet.
Resistance at 15°C = .01763 x 1022 = 18.0 ohms.
* Ohmic Drop at no load = 18.0 x .035 = .63

Secondary
Length of mean turn = 30.8 cms
Length of secondary wire = 30.8 x 2980
= 91,750 cms
= 36,100 inches
= 3010 feet
Gauge = 28 (DCC)
Resistance at 60°F = .04636 x 3010
= 140.0 ohms.
  
  
From the Rolls-Royce experimental archive: a quarter of a million communications from Rolls-Royce, 1906 to 1960's. Documents from the Sir Henry Royce Memorial Foundation (SHRMF).