Rolls-Royce Archives
         « Prev  Box Series  Next »        

From the Rolls-Royce experimental archive: a quarter of a million communications from Rolls-Royce, 1906 to 1960's. Documents from the Sir Henry Royce Memorial Foundation (SHRMF).
Test procedures for an electrical distributor and contact breaker.

Identifier  ExFiles\Box 69\1\  scan0187
Date  19th February 1929 guessed
  
-2- Contd.

in circuit with the 12 volt battery, ammeter, and contact
breaker, just permits the passage of 1.00 ampere when the
contacts are closed. The make ratio of the distributor
can then be set by adjusting and locking the contact points
in such a position as to permit the passage of .55 ampere
with the contact breaker running at 700 r.p.m. (This averages
out any slight differences in the gaps due to the six points of
the cam). The test consists of a preliminary run of 5 mins.
at 700 r.p.m. under above conditions, with the spark gaps
set to 5.5 mm.

(4) This test consists in running for 5 mins. under
working conditions, i.e. on 12 volts, but with the high
tension wire disconnected from the cold, i.e. with the second-
ary open circuited. The running current at the end of this
test must not exceed 1.20 amperes. During the test, a
distributor H.T. rotor may also be tested (for insulation)
as described under distributor production test.

(5) The H.T. wire shall now be reconnected to the
xoil and a further test of 15 mins. under normal conditions
but at 10 volts with 5.5 mm. gaps shall take place, during
which time no missing⁺ shall occur at the gaps, and the
running current at the end of the test shall be between the
limits .94 and 1.02 ampere.

FFC.

+ There shall be considered to be no missing when,
at some time within a period not greater than
one minute, 500 consecutive sparks take place.
  
  


Copyright Sustain 2025, All Rights Reserved.    whatever is rightly done, however humble, is noble
An unhandled error has occurred. Reload 🗙