Fusing current for main and distributing fuses and the specifications for ammeters.

Identifier  ExFiles\Box 61\2\  scan0492
Date  19th September 1928
  
To R.{Sir Henry Royce} from EFC.
c. c. E.{Mr Elliott - Chief Engineer} BJ. BY.{R.W. Bailey - Chief Engineer}

X2515
X9780

EFC3/T19.9.28.

Referring to your R1/M18.9.28 and in particular the fusing current of main and distributing fuses, the fusing current of 15 amperes for 30 S.W.G. copper wire is for an indefinitely long length. For the length we use in our fuse holders the fusing current is more like 28 amperes, so that the fusing current of the main fuse is something less than 3 x 28 amperes, viz, about 80 amperes. Because the ammeter may have to carry this current if a dead earth occurs on the wiring we specify that the ammeters must stand without damage a current of 90 amperes for 3 seconds each way.

EFC.
  
  