Test procedures for a main switch, specifying current, voltage, and pressure parameters.

Identifier  ExFiles\Box 64\3\  scan0216
Date  9th March 1926 guessed
  
-3- Contd

(5) Verify that the main spring tension (combined rating and set) is such that a current of not more than 1.5 amperes through the coil and non-inductive resistance in parallel is necessary to pull the switch arm over from the "off" position.

(6) It must further be confirmed by means of a spring balance that the combined rating and set of the spring is such that this main switch is definitely capable of holding on contact with a copper contact pressure of at least 2.0 lbs., when a current of 3.0 amperes, inclusive of the current passing through the parallel non-inductive resistance, is supplied toit.

(7) While still warm from test (6), an alternating voltage of 205 shall be applied, through a lamp, between the windings (including the non-inductive resistance coil) and the switch arm; and also between the main switch contact pillar and the switch arm; for one minute with-out breakdown.

(8) The final test of the main switch is to consist of the testing under approximate working conditions as described in Section III.

Contd.
  
  