Winding specifications for an auto-transformer used in the production testing of condensers.


Identifier  ExFiles\Box 32\4\  Scan005
Date  4th September 1919
  
EFC {E. Fowler Clarke - Electrical Engineer} /T4.9.19.

WINDING OF TRANSFORMER FOR PRODUCTION TESTING OF CONDENSERS.

The transformer is to be wound as an auto-transformer, that is to say, one continuous winding, but with tappings giving 110, 220, 350, 400 and 450 volts according to the scheme below:-

[DIAGRAM OF A CONTINUOUS COIL WITH TAPPINGS]
Coil Sections: A, A, B, C, C
Voltage Differences between taps: 110, 110, 130, 50, 50
Voltage at taps: 0, 110, 220, 350, 400, 450 VOLTS

Each A coil is to consist of 440 turns of 21 gauge (.032") D.C.C. wire.
B coil is to consist of 520 turns of 21 gauge / D.C.C. wire, and the two C coils are/to consist of 200 turns of 22 1/4 gauge (.026") D.C.C. wire.

The 6 Terminals are to be conveniently arranged, three on each side of the transformer.

The actual details of the insulation we will leave to your winder.

EFC. {E. Fowler Clarke - Electrical Engineer}